MOXA PT-G503-PHR-PTP
IEC 61850-3/62439-3 3-port full Gigabit managed redundancy boxes
- IEC 61850-3, IEEE 1613 (power substations) compliant
- IEC 62439-3 Clause 4 (PRP) and Clause 5 (HSR) compliant
- PRP/HSR Coupling and QuadBox functions supported
- Ethernet console reserved for local access ››Built-in MMS server, based on IEC 61850-90-4 switch modeling for power SCADA
- Hardware-based IEEE 1588v2 PTP supported
- Design ready for NERC CIP compliance system development
- Isolated redundant power inputs with universal 24/48 VDC or 110/220 VDC/VAC power supply range
- -40 to 85°C operating temperature range
The PT-G503-PHR-PTP series redundancy boxes (RedBoxes) are compliant with the latest standardized redundancy protocols for industrial automation networks, IEC 62439-3 Clause 4 (Parallel Redundancy Protocol, PRP) and IEC 62439-3 Clause 5 (High-availability Seamless Redundancy, HSR). PRP/HSR ensures the highest system availability and data integrity for mission-critical applications in electrical substation and/or process automation systems that require zero recovery time redundancy. The redundant protocols Coupling and QuadBox are also supported. With Coupling and QuadBox, HSR rings can be connected to make the redundant network more versatile. The PT-G503-PHR-PTP series comes with three 10/100/1000BaseT(X) and 100/1000BaseSFP slot combo ports.
One slot (INTERLINK port) is for an internal link for connecting with a SAN (Singly Attached Node). The other two ports (LAN A and LAN B ports) are for PRP/HSR redundant protocol communications. With this full Gigabit Ethernet port design, the PT-G503-PHR-PTP series provides high performance for PRP/HSR systems.
The PT-G503-PHR-PTP series also provides hardware-based IEEE 1588v2 PTP when in end-to-end one-step transparent clock mode for timing-critical applications and isolated redundant power inputs with 24/48 VDC or 110/220 VDC/VAC power supply ranges to increase the reliability of the power supply.
Technology
- Standards
IEEE 802.3 for 10BaseT
IEEE 802.3u for 100BaseT(X) and 100BaseFX
IEEE 802.3ab for 1000BaseT(X)
IEEE 802.3z for 1000BaseX
Software Features
- Management
IPv4/IPv6, PRP/HSR, SNMPv1/v2c/v3, DHCP Client, BootP, SMTP, RARP, HTTP, Telnet, LLDP, Flow Control, Back Pressure Flow Control, SNMP Inform, Port Mirror, Fiber Check, Syslog, RMON
Filter
Multicast Filter Behavior
Redundancy Protocols
PRP/HSR, RSTP Transparent
Security
RADIUS, TACACS+, Trusted Access Control, Authentication Certificate (SSL Certificate, SSH Key Regenerate)
Time Management
SNTP, NTP Server/Client, IEEE 1588v2 PTP
Industrial Protocols
Modbus/TCP
MIB
IEC 62439-3 MIB
Power Substation
MMS
Interface
- Gigabit Ethernet
- +13 to +30 V for state “1”
- -30 to +3 V for state “0”
- Max. input current: 8 mA
3 x 10/100/1000BaseT(X) ports or 100/1000BaseSFP combo ports
Console Port
Ethernet console (10/100/1000 Mbps RJ45), USB-serial console (Type B connector)
Storage Port
USB storage (Type A connector for ABC-02-USB)
Alarm Contact 1 relay output with current carrying capacity of 1 A @ 24 VDC
Digital Inputs
1 input with the same ground, but electrically isolated from the electronics
Power Requirements
- Input Voltage
- WV: 24/48 VDC
- HV: 110/220 VDC/VAC
- WV: 18 to 72 VDC
- HV: 88 to 300 VDC, 85 to 264 VAC
- Max. 0.660/0.360 A @ 24/48 VDC
- Max. 0.150/0.080 A @ 110/220 VDC
- Max. 0.260/0.170 A @ 110/220 VAC
Operating Voltage
Input Current
Overload Current Protection
Present
Connection
5-pin terminal block
Reverse Polarity Protection
Present
Physical Characteristics
- Housing
Aluminum alloy
IP Rating
IP40 protection
Dimensions
80 x 160 x 110 mm (3.15 x 6.30 x 4.33 in)
Weight
1210 g (2.69 lb)
Installation
DIN-rail mounting
Environmental Limits
- Operating Temperature
-40 to 85°C (-40 to 185°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
5 to 95% (non-condensing)
Standards and Certifications
- High Availability Automation Networks
IEC 62439-3
Safety
UL 508
EMI
FCC Part 15 Subpart B Class A, EN 55022 Class A
EMS
IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 35 V/m
IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV
IEC 61000-4-5 Surge: Power: 4 kV; Signal: 4 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8
IEC 61000-4-11
Rail Traffic
EN 50121-4
Electrical Substation
IEC 61850-3, IEEE 1613
MTBF (mean time between failures)
- Time
PT-G503-PHR-PTP-WV:440,857 hrs
PT-G503-PHR-PTP-HV:566,844 hrs
Standard
Telcordia TR/SR
Ordering Information
Available Modules | |
PT-G503-PHR-PTP-WV | IEC 61850-3 and IEC 62439-3 full Gigabit managed redundancy box, with 3 10/100/1000BaseT(X) ports or 100/1000Base SFP ports, 1 10/100/1000BaseT(X) Ethernet console port, 1 isolated dual power supply(24/48 VDC), -40 to 85°C operating temperature |
PT-G503-PHR-PTP-HV | IEC 61850-3 and IEC 62439-3 full Gigabit managed redundancy box, with 3 10/100/1000BaseT(X) ports or 100/1000Base SFP ports, 1 10/100/1000BaseT(X) Ethernet console port, 1 isolated dual power supply(88 to 300 VDC or 85 to 264 VAC), -40 to 85°C operating temperature |