Raritan PX2-2297

Monitored and switched rack power distribution unit
(0U [vertical], 7.4kVA, 12 outlets)

Raritan PX2-2297
6105_19295.png
6105_19296.jpg
6105_19297.jpg
  • DescriptionDescription
  • Further InformationFurther Information
  • PDFPDF

Monitored and switched rack power distribution unit (0U [vertical], 7.4kVA, 12 outlets).


INPUT:
230v, 32a - IEC 60309 2P+E 6h 32A plug (2P3W);

OUTPUT:
8@ C13, 4@ C19 outlets; on 2@ 1-pole, 16a Overcurrent Protectors;

FEATURES:
Billing-Grade (+/- 1%) Energy Metering [kW, kVA, V, A, Power Factor] - per inlet, per breaker/fuse;
Remote Outlet Switching (Normally-Open Relays); 3-digit LED user-selectable display (voltage, current, or active power : per line or per breaker).
Local display of alarms and configuration information(name, ratings, IP/Networking);
Onboard embedded processor with minimum 400MHz clock speed, 16MB NOR Flash, and 64MB SDRAM;
Remote network monitoring via HTML, JSON-RPC, SSH, Telnet, MODBUS/TCP, and SNMPv3.
Environmental monitoring [temp/humidity] capable of up to 32 sensors.
Individual outlet numbers labeled on chassis.
Automated deployment via TFTP, DHCP/PXE, SSH(CLI), or USB Flash Drives.
WiFi Capable.
USB Webcam Capable.
iPad/iPhone/Android App.
Breaker metering and alarming (0V detection).
Max Dimensions 52 mm x 65 mm x 1298 mm (2.06in x 2.57in x 51.10in).
Max Weight 7.5 kg.
Maximum ambient temperature 50C at full load.
ProdGrafik
Features

    Energy Metering
    Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor

    Metering Accuracy
    ISO/IEC 62053-21 1%

    Remote Outlet Switching
    Yes

    Metering per input line
    Yes for all models

    Metering per Branch Circuit Breaker
    Yes

    Environmental Sensor Ready
    Yes

    Compatible Sensors
    Temperature, Humidity, Air Flow, Differential Pressure, Water Leak, and Contact Closure.

    Cascading
    Yes, Max 16 PDUs can be daisy chained using a USB connection.
    Note: Firmware version 3.3.10 or above is required.

    Networking
    10/100/1000 BaseT Ethernet.
    Optional WiFi (802.11a/b/g/n).

    Onboard Display
    3-digit LED user-selectable display (voltage, current, or active power : per line or per breaker).
    Auto-flip orientation




Specifications

    Input

      Input Plug
      IEC 60309 2P+E 6h 32A (2P3W)

      Nominal Voltage
      230V

      Maximum Input Current
      32A

      Rated Input Current
      32A

      Power Capacity
      7.4kVA

      Cord Length
      3m



    Output

      Nominal Voltage
      230V

      Receptacles (Output Connections)
      (8) IEC320 C13
      (4) IEC320 C19

      Overload Protection
      (2) Airpax LEGBX6-37483-16-V



    Physical

      Dimensions (WxDxH)
      2.06in x 2.57in x 51.10in; 52 mm x 65 mm x 1298 mm

      Unit Weight
      7.5 kg

      Shipping Weight
      9.5 kg

      Shipping Dimensions
      280mm x 115mm x 1420mm

      Mounting
      G2-RACK-FOR-ZU



    Environmental

      Operating Temperature/Environment
      50 C

      Operating Relative Humidity
      85%

      Operating Elevation
      0-10000ft



    Conformance

      Regulatory Approvals
      CE